| Interface | IO-Link 1.1 |
| Operating voltage Ub | 18…30.2 VDC |
| Connection (COM 1) | M12x1-Male, 4-pin, A-coded |
| Connection slots | 8x M12x1-Female, 5-pin, A-coded |
| Digital inputs | 16x PNP, Type 3 |
| Digital outputs | 16x PNP |
| Configurable inputs/outputs | yes |
| Single-channel monitoring | yes |
| Additional function | Identification 2 bytes |
| Current sum US, sensor | 4 A |
| Switching current | 16x 350 mA |
| Current sum UA, actuator | 4 A |
| Housing material | PA, Transparent |
| Dimension | 50 x 30.8 x 115 mm |
| Ambient temperature | -5…55 °C |
| IP rating | IP67, when threaded in |
| Transfer rate | COM2 (38.4 kBaud) |
| Process data cycle min. | 5.5 ms |
| Process data IN | 10 bytes |
| Process data OUT | 2 bytes |